Home > Sample essays > Breifly analyse for a two system connected through a line using SVC…Optimize Transient stability using SVC in IEEE-9 Bus System

Essay: Breifly analyse for a two system connected through a line using SVC…Optimize Transient stability using SVC in IEEE-9 Bus System

Essay details and download:

  • Subject area(s): Sample essays
  • Reading time: 7 minutes
  • Price: Free download
  • Published: 1 April 2019*
  • Last Modified: 23 July 2024
  • File format: Text
  • Words: 2,002 (approx)
  • Number of pages: 9 (approx)

Text preview of this essay:

This page of the essay has 2,002 words.



TRANSIENT STABILITY ANALYSIS USING SVC IN IEEE-9 BUS SYSTEM

Ramakanta Jena*,Shaswat Chirantan**,Dr.P.C.Panda***Dr.S.C Swain

*PhD.S O. E. E,KIIT University,Bhubaneswar,India

**M.Tech Scholar, S O. E. E,KIIT University,Bhubaneswar,India

*** Professor, S O. E. E,KIIT University,Bhubaneswar,India

Abstract The Power system Transmission networks are becoming  complexity due to growing demand and restrictions on building new lines. Losing stability is one of the major problem of such a modern power system following a disturbance. FACTS technologies are found to be very effective in a power system transmission network for better controllability and increase power transfer capability without sacrificing the desired stability margin.Also FACTS (SVC) technology provides new opportunity for contolling power and enhancing stability at present as well as building upgraded lines for normal and fault conditions

Keywords—Transient stability,FACTS,SVC

Introduction

The power system operation consists of Three stages of operation i.e Generation ,Transmission And Distribution.The important thing in Power system is to maintain continuous Power supply,which retains stability of voltage but due to unexpected events such as faults, the generators are disturbed causing lack of proportion between generation and load demand.So Fault must be cleared within specific time in order to protect damage to the line Equipment ,which leads to power loss and system outage.

POWER SYSTEM STABILITY

This is the ability of a Power system to regain its normal operating point after being subjected to a physical disturbance .

Stability may be classified   depends on the

1. Instability of system i.e

Voltage, Frequency instability

2. Size of the disturbance

Small, large disturbance

3. Time frame of stability  

Short and Long term.

 In the other hand, stability broadly classified as

 1. A. Steady state stability

   B. Dynamic stability.

A. Steady State Stability .It is the capability of the system to retain in regular or continuous from  one operational state to another under the condition of small load changes.

B.  Dynamic stability It is the rotor angle stability   after being subjected to a disturbances .

2. Transient   Stability. Transient instability occurs when a large disturbance such as loss of load, fault and  loss of generation etc., occurs the power balance is upset and the generating units rotors experience either acceleration or deceleration. or

Transient stability is the capaability of the power system to retain the state of operational equilibrium under large disturbances.Large disturbances may be considered as L-G,LL-G,LLL-G,line to line fault or sudden change in heavy loads.These cause the power system to oscillates & swings around stability limits.If power system cannot achieve stability limit then system loses synchronism.Alternator will draw power from the power system & deteriorates the functionality of the electrical grids.

OBJECTIVES OF SHUNT COMPENSATION

The Voltage Profile and Steady state Power transfer can be increased by using Shunt Compensating devices. Shunt compensation improves improves transmission characteristic as well as improves stability of the system.Var compensation is used at mid point for voltage regulation and at the end  voltage instability is prevented to damp power system oscilltations.

An Ideal Shunt Compensator  

1.Improves Voltage Profile

2. Improving Power-Angle Characteristics

3.Improving Stability Margin

   4.  Improving Damping of Power Oscillations

FACTS CONTROLLERS.

The FACTS controllers are static and flexible  controllers which provides controllability and improve power transfer capability.

SVC(STATIC VAR COMPENSATOR)

  SVC is basically a shunt based FACTS controller  whose output is varied  to maintain specified parameters such as bus voltage by exchanging inductive and capacitive current.It consists of TCR/TSR for absorbing reactive var & TSC for injecting reactive vars.As we know voltage instability is caused by reactive power mismatch.So Static Var Compensator can compensate the need of reactive var to the system.It has also the capability of being used as certain filter by tuning capacitor & inductor switching circuit modeled as filter elements[13].

Figure.1-Static Var Compensator

CONCEPT OF  TRANSIENT STABILITY IMPROVEMENT:

 Compensation using FACTS change the power flow during dynamic disturbances in order to improve the Transient stability and damp power system oscillation. This is described by the equal area criterion.This criteria is explained below by taking a two machine two line system. The corresponding power (P) and Transmission angle(δ) curve is shown below.

    

   Figure-2  Figure3

The P versus   delta (δ)  curve “a” is operated at an angle delta1 δ1 before the fault . During the fault the system is characterized by curve b and during this period the transmitted power decreases  and mechanical input power to the machine remains constant which is shown by the line P1 .So the generator accelerates and (δ) increases delta1 to delta2 from where the the faulted line  is disconnected . A1 represents the accelerating energy  which is absorbed by the sending end generator. After clearance of the fault  the system is characterized by the curve c. From delta2 the transmitted power exceeds P1 and sending end machine(generator ) starts to decelerate, but the transmission angle increases due to stored kinetic energy. At delta3  ,the decelerating energy is given by the area A2  become equal to accelerating energy A1.The transient stability limit is reached at delta3=delta critical beyond which decelerating energy would not balance the accelerating energy  and synchronism between sending end receiving end could not be restored. Amargin represents the transient stability margin.

Hence It is clear from the above that the transient stability is determined by the  P and  delta  curve of post fault system.

   SVC works in a superior manner when installed at middle of the transmission line which connects two systems.Thus SVC operates as a midpoint shunt compensator & accordingly enhances the maximum power transfer,nodal voltage support,transient stability limit & power oscillation damping.From the concept of equal area criterion we can clearly analyze the improvement of transient stability margin bu shunt compensation in a two area system[10] as depicted in figure.4.Static Var Compensator has two modes of control strategy,one is Var control mode & other is Voltage regulation mode.Var control mode can be activated by varying susceptance(Bref) value & Voltage regulation mode is controlled by a reference voltage(Vref)  & a voltage regulator unit.Transient stability improvement & power oscillation damping is operated by voltage regulation mode.

(a)  (b)

Figure.4-Transient stability margin of a two machine system (a)without compensation(b)with midpoint compensation

A1 & A2 are accelerating & decelerating energy represented by areas without compensation.Ap1 & Ap2 are accelerating & decelerating areas with midpoint compensation.Similarly we can see the transient stability margin Amargin(uncompensated system) & Apmargin(midpoint compensated system).

CHARACTERISTIC OF SVC

SVC is composed of a shunt capacitor(thyristor switched capacitor) and a shunt reactor  thyristor switched reactor.

SVC operates in two modes i.e in Var control mode(where susceptance is fixed) and in Voltage control mode (where voltage can be controlled within limits)

    

    Figure-5  Figure-6

Generally, A SVC gives near about  constant voltage, and possess maximum VAR absorption/generation capability . The performance of the SVCcan be  seen in Figure (6).

In below fig the characteristics of SVC  is shown in Figure (7).The   compensating  current   decreases linearly and maximum var output decreases with square of AC voltage,as shown in fig below

 

  Figure-7  Figure-8

POWER OSCILLIATION DAMPING

The Below Fig. shows Power oscillation damping of transmission angle   and steady state value .

  Figure-9  

MATHEMATICAL  INTERPRETATION

The swing equation of a electrical machine indicates the dynamic behavior.The Dynamic behavior of an n-generator power system can be described by the following equations

 ……………….1

   ………………………2

 ……………..3

   ………………4

where

  M-moment of inertia of machine

   – rotor angle of machine

    =   1-  2  

   Pm- Mechanical Power output

  Pe- Electrical Power output

  Pa- Accelerating Power

  – synchronous speed/Rotor speed in electrical  degrees

DATA SHEET FOR THE STUDY

   Table-1 Generator, Transformer, & SVC Parameters

Table-2-Transmision Line and Load parameters

Table-3 Bus data

POWER SYSTEM STUDY

The Matlab simulink is used to analyze the transient stability of  IEEE 9-bus  multi machine  power system .The Operation is carried out for two generators at nominal loading and one at Heavy loading condition.The base MVA and system frequency are considered to be 100 MVA and 60 Hz, respectively. The generator M1 is connected to slack bus 1, generators 2 (M2) and 3 (M3) are connected to bus bars 2 and 3, respectively. Loads A, B and C are connected in bus bars 5, 6 and 8 respectively. The transient stability analysis is  being  carried out  by monitoring the performance of the generators (M1, M2 and M3) and at different buses. The analysis of this  system  have been considered when three phase fault occurs in the network.

A.ANALYSIS WITHOUT FAULT

The fig below shows a simulink diagram of  IEEE-9bus system. First the Rotor speed is analyzed without fault and found  very less fluctuation initially then the system becomes steady quickly.

 

  Figure-10

Relative Rotor angle of Machine 2 w.r.t Machine 1, Machine 3 w.r.t Machine 2 and Machine1 w.r.t Machine3.(Before fault)

B. ANALYSIS WITH THREE PHASE FAULT AT LINE 6(BETWEEN BUS 8 AND 9)

Figure-11

Here a  Three phase fault (LLL-G) is considered at Bus -9 in Line 6 for a duration of 0.1 second.and the fault is cleared at the same 0.1 second so the system stability is being Affected.The rotor speed of Machine 3 w.r.t Machine 2 and machine 1 fluctuates more as fault is occcured near the Machine 3 .Then the system becomes steady.

The relative rotor angle delt2_1, delt3_2and delt1_3 of IEEE 9 bus system with fault at line 6 and  without SVC

C.ANALYSIS WITH THREE PHASE FAULT AT LINE 6(BETWEEN BUS 8 AND 9) WITH SVC AT BUS 8-9

The relative rotor angle delt2_1, delt3_2and delt1_3 of IEEE 9 bus system with fault at line 6 and  with SVC.

Here SVC is connected in line-6 i.e between Bus 8 and 9 and the variation of Rotor speed is shown in fig above.

COMPRASION

Conclusion

From the overall analysis we can see that power system stabilizer & static var compensator are invariably designed for system stability enhancement.In the other way SVC enhances the system stability by regulating the bus voltage specified by voltage regulation mode.From the comparision it is clear that SVC gives the better Result.

References

[1] S. Gilbert, "transient stability of a two-machine transmission system with power system stabilizers (PSS) and Static Var Compensator (SVC)", Hydro-Québec SimPowerSystems (Guid's) MathWork MATLAB Simulink version 7.2.0, 2010.

[2] M. Mohammad, "Voltage stability analysis with static Var compensator (SVC) for various faults in power system with and without power system stabilizers (PSS)", Research Journal of Applied Sciences Engineering and Technology, vol. 3, no. 7, pp. 668-676, 2011

[3] K. Alok, D. Surya Bhushan, "Enhancement of transient stability in transmission line using SVC facts controller", International Journal of Recent Technology and Engineering, vol. 2, no. 2, May 2013

[4] Ali, "Development of system with transitory steadiness of a bi-machine transmission system with power system stabilizers and static Var compensator", International Journal of Engineering Research and Applications, vol. 3, no. 3, pp. 1121-1125, May-Jun 2013

[5] Benaissa, Omar Mohammed, Samir Hadjeri, and Sid Ahmed Zidi. "Impact of PSS and SVC on the power system transient stability." Modelling, Identification and Control (ICMIC), 2016 8th International Conference on. IEEE, 2016.

[6] Shahgholian, Gh. "Review of power system stabilizer: Application, modeling, analysis and control strategy." International Journal on Technical and Physical Problems of Engineering 5.3 (2013): 41-52.

[7] Shahgholian, Ghazanfar. "Power system stabilizer application for load frequency control in hydro-electric power plant." Journal of Theoretical and Applied Mathematics. Vol 3.4 (2017): 148-157.

[8] Mahmud, M. A., M. J. Hossain, and H. R. Pota. "Effect of large dynamic loads on interconnected power systems with power oscillation damping controller (PODC)." Power Engineering Conference (AUPEC), 2010 20th Australasian Universities. IEEE, 2010.

[9] Kar, P., Panda, P. C., Swain, S. C., & Kumar, A. (2015, October). Dynamic stability performance improvement of SMIB power system using TCSC and SVC. In Power, Communication and Information Technology Conference (PCITC), 2015 IEEE (pp. 517-521). IEEE.

[10] Xiaolu Li, Lixin Bao, Xianzhong Duan, Yangzan He and Mingyan Gao.:”Effects of FACTS Controllers on Small-Signal Voltage Stability” IEEE Transaction-2000.

[11] Panda, Sidhartha, Srikanta Mahapatra, and S. C. Swain. "Modelling, simulation and optimal tuning of FACTS controller in a multi-machine power system." International Journal of Applied Systemic Studies 6.1 (2015): 42-57

[12] P.Kundur, “Power System Voltage Stability and Control”, McGraw-Hill, ISBN 0-07-035958-X, 1994.

[13] N.G. Hingorani, L. Gyugyi, “Understanding FACTS, Concepts and Technology of Flexible AC Transmission Systems”, IEEE Press, 2000.

ere…

About this essay:

If you use part of this page in your own work, you need to provide a citation, as follows:

Essay Sauce, Breifly analyse for a two system connected through a line using SVC…Optimize Transient stability using SVC in IEEE-9 Bus System. Available from:<https://www.essaysauce.com/sample-essays/2018-11-10-1541840417/> [Accessed 14-06-26].

These Sample essays have been submitted to us by students in order to help you with your studies.

* This essay may have been previously published on EssaySauce.com and/or Essay.uk.com at an earlier date than indicated.